Types
of Utility
|
Standard
|
Site
Area Required
|
Minimum
Width of access
|
Minimum
safety clearance
|
Maximum
gradient of access
|
| Electricity Supply |
| Extra High Voltage Substations |
6500m2
(100m x 65m)
|
6.5m
|
200m away from telephone exchange, broadcasting or radio communication
installation
|
1 in 12
|
| Bulk Infeed Substations
(a) in CLP Power network
(b) in HEC network :
(i) 275kV Station
(ii) 132kV Station
|
2870m2
(70m x 41m)
1504m2
(32m x 47m)
2550m2
(30m x 85m)
|
4.5m
4.5m
4.5m
|
1 in 10
1 in 10
1 in 10
|
| Primary Substation (Zone
Substations)
(a) in CLP Power network
(b) in HEC network
|
1705m2
(55m x 31m)
1600m2
(40m x 40m)
|
4.5m
4.5m
|
1 in 10
1 in 10
|
Consumer's Substation
(Distribution
Substation)
(a) Indoor Type
(b) Outdoor Type
|
30.25m2
(5.5m x 5.5m)
51m2
(8.5m x 6m)
|
3m
3m
|
-
-
|
-
-
|
Overhead
Transmission Lines
(a)
400kV
(b) 132kV
(c)
66kV
(d)
33kV
(e)
11kV
|
-
-
-
-
-
|
6m; may be required to
reach the principal
face of any adjacent building
development for fire fighting purpose
|
Horizontal : 5.5m
Vertical : 7.6m
Horizontal : 3.7m
Vertical : 6.7m
Horizontal : 3.2m
Vertical : 6.1m
Horizontal : 2.9m
Vertical : 6.1m
Horizontal : 2.9m
Vertical : 6.1m |
|
| Underground
Cables |
no
set standard
minimum separation between power cables and
telephone cables is 0.3m wherever practicable.
|
| Gas
supply |
no
set standard |
| Telephone
Services |
|
Telephone
Exchange
(a)
local exchanges in rural areas with <10,000
lines
(b)
local exchanges in urban area with
20,000 - 60,000 lines
(c)
local exchange in
urban areas with >120,000 lines
or combined local/ tandem exchanges
or telephone exchange complexes
|
500m2
1000m2 -
1500m2
1500m2 -
2000m2
|
-
-
-
|
at least 200 m
away from any power
generating station,
bulk infeed substation or
primary station
|
-
-
-
|
| Telephone
cables |
a
minimum separating distance of 2.5m from the
nearest Light Rail Transit System and 300m from
Kowloon Canton Railway System.
|